How to install a Power Control Unit (Energy Management)

A Power Control Unit (PCU) is the digital twin of a controlled space — a hotel room, an apartment, a sports court, a meeting room or a common area. It groups all the devices that serve that space, so that Luckey can switch its electrical power on and off from access events, manual commands and, with Energy Management Ultra, the real presence of people.

This guide is written for installers, electricians and the engineer who prepares the site survey. It covers the whole installation, from the survey to the final test.

Before you start: how a Power Control Unit is built

Two rules shape the whole installation:

  1. One HyperGate controls one Power Control Unit. Every unit needs its own HyperGate: do not plan a gateway that serves two rooms.
  2. Every device of a unit talks to its HyperGate over Bluetooth LE. The Smart Relay, the HyperRadar, the HyperSensor DS contacts and the trigger locks must all be within reliable radio range of the same HyperGate. There is no cable between them and the gateway, and the automation runs on the HyperGate.

The Energy Management add-on must be enabled on your Luckey system. The available functions depend on the edition: Smart (power follows the user) or Ultra (power follows the people, with the HyperRadar presence sensor). A unit with at least one HyperRadar requires the Ultra subscription; without HyperRadar, Smart is enough

What goes into one unit

DeviceCodeQuantity per unitWhere it goesPower
HyperGate (DIN, Lite WiFi or Lite PoE)004S103.DIN · 5E07S524 · 5E07S5141Near the space, within radio range of all its devicesDepends on the model (see Step 2)
Smart Relay BLE (Argo)5E0655021Electrical cabinet24 V DC from power supply 5E3506
Power supply 24 V DC – 30 W5E35061Electrical cabinet230 V AC
HyperRadar presence sensor (Ultra only)004S1180–1Ceiling, 2.5–4.0 m12 V DC / 1 A adapter included in the box
HyperSensor DS door and window contact (optional)004S1080–4On doors and windowsBattery
HyperTag (optional)004S1010–1At the entrance of the spaceNone
Trigger locks—As in the access control projectOn the doors of the spaceBattery

Step 1 — Survey the site

Walk every space before you install, and note the following:

  • Electrical cabinet: where it is, whether it is metallic, and how far it is from the room. You need room for one Smart Relay and its 24 V DC power supply for each unit.
  • Load to switch: what the relay must control (lighting, HVAC, sockets) and the current it draws. Check it against the contact rating in the Smart Relay data sheet. For HVAC and heavy loads, the relay drives a contactor and does not switch the load directly.
  • HyperGate position: one per unit, within range of the cabinet (relay), the ceiling (radar), the door and window contacts and the trigger locks.
  • Ceiling height (if a HyperRadar is planned): it must be between 2.5 m and 4.0 m.
  • Room length and width (if a HyperRadar is planned): check that one sensor covers the room, see Step 4.
  • Mains outlet at the ceiling for the HyperRadar 12 V adapter.
  • Doors and windows to monitor with HyperSensor DS to cut the power when they are open, up to 4 per unit.
  • Sources of interference below the radar: metal objects, ceiling fans, moving curtains, plants, large glass or mirror surfaces.

Step 2 — Install the HyperGate

  1. Place the HyperGate as close as possible to the centre of the unit's devices. The relay in the cabinet and the radar on the ceiling are usually the furthest apart: check the range to both.
  2. Avoid metal enclosures, thick concrete walls and lift shafts between the HyperGate and its devices.
  3. Power it according to the model:
ModelCodePower
HyperGate Lite WiFi5E07S524Power supply 0000A00155. Wall-mounting kit 0000A00154
HyperGate Lite PoE5E07S514PoE switch IEEE 802.3af over CAT5e or CAT6. Wall-mounting kit 0000A00154
HyperGate DIN004S103.DINDIN-rail installation, see the HyperGate DIN technical sheet
  1. Give each HyperGate a clear name that matches the space, for example Room 101 · HyperGate. It makes the association in Luckey Tools much easier.

Step 3 — Install the Smart Relay in the electrical cabinet

The relay physically switches the load: a lighting circuit, a sockets circuit or the contactor of an HVAC system. The electrical work must be done by a qualified electrician, with the circuit isolated, and in compliance with local regulations.

  1. Mount the 24 V DC power supply 5E3506 (230 V AC in, 24 V DC out, 30 W) and the Smart Relay BLE 5E065502 in the cabinet.
  2. Wire the power supply output to the Smart Relay power input, respecting the polarity: +24 V and 0 V.
  3. Wire the normally open (NO) contact of the relay in series with the circuit to switch:
    • Lighting and sockets: directly, only if the load is within the contact rating.
    • HVAC and heavy loads: to the coil of a contactor, which switches the load.
  4. The Smart Relay has a 3 m antenna. If the cabinet is metallic, route the antenna outside the cabinet, so that the HyperGate can reach the relay.
  5. Label the relay with the name of the unit.

Step 4 — Install the HyperRadar presence sensor (Ultra only)

Check the coverage first

One HyperRadar mounted on the ceiling covers a circle of 6 m diameter on the floor (about 28 m²), at any height between 2.5 m and 4.0 m (coverage as per the Minew MSR01 specification).

A rectangular room is fully covered by one sensor placed at its centre only if its diagonal is 6 m or less:

RoomDiagonalOne HyperRadar?
4.0 × 3.5 m5.3 mYes
4.8 × 3.6 m6.0 mYes, just enough
6.0 × 3.0 m6.7 mNo: split into 2 units
6.0 × 4.5 m7.5 mNo: split into 2 units of about 3 × 4.5 m

A unit has one presence sensor. If a room is too large, split it into several units, each with its own HyperRadar, Smart Relay and HyperGate.

Mount the sensor

  1. Choose the position: on the ceiling, ideally at the centre of the area to cover, between 2.5 m and 4.0 m high. The area below the sensor must be free of metal objects and obstructions.
  2. Orient the base: the arrow on the base must be parallel to one of the walls. It defines the X and Y axes used for the exclusion zones.
  3. Fix the base:
    • With screws (cable coming from the ceiling): pass the power cable through the central hole of the base, then fix the base with the 4 self-tapping screws and wall plugs supplied. This is the recommended method.
    • With the adhesive kit (cable coming from the side): stick the double-sided adhesive on the base, route the DC cable through the groove of the adhesive and press the base on a clean ceiling for 5–10 seconds.
  4. Connect the power: plug the 12 V DC / 1 A adapter included in the box into the mains outlet at the ceiling. Insert the DC wires into the terminal, respecting the + and − marks on the housing. Pull gently: if the wire does not come out, it is fixed correctly.
  5. Close the sensor on its base. The connection is magnetic and the sensor can rotate 360°. The LED flashes red once at power-on.
  6. With the mobile application, set the installation height and the detection zone.

HyperRadar is a 60 GHz radar: it detects the person and not only the movement, so someone reading, sleeping or watching TV is still detected. It is completely anonymous: no camera, no images, no personal data.

Avoid false detections

  • Do not point the sensor at doors, windows, curtains or plants that move.
  • You can define up to 6 exclusion zones for doors and windows (coordinates within ±3 m of the sensor). Movement outside the line joining two points is ignored.
  • If reflective surfaces cause false detections (screens, glass, smooth walls, metal), enable the self-learning function of the sensor with the room empty.
  • Operating range: −10 °C to +45 °C, 95 % relative humidity or less, non-condensing. HyperRadar is an indoor sensor and is not suitable for outdoor courts.

Step 5 — Add door and window sensors, the HyperTag and the trigger locks

HyperSensor DS (optional)

  • Install one contact for each door or window you want to monitor, up to 4 per unit.
  • When a monitored opening is left open, the unit switches off and stays inhibited until it closes. It stops air conditioning running against an open window.
  • The contacts are battery-powered and talk to the HyperGate over Bluetooth LE: check the radio range from every window.

HyperTag (recommended)

  • Place it at the entrance of the space, where users naturally stop and can scan it with the Luckey app. It needs no wiring.
  • Authorized users switch the space on and off by scanning it with their smartphone.

Trigger locks

  • The locks of the space can switch the unit on (entry) or off (exit). They are usually already part of the access control project.
  • They must be associated with the same HyperGate as the rest of the unit.

Step 6 — Create the Power Control Unit in Luckey Tools

With the Luckey Tools application, create the Power Control Unit and give it the same name as the space (for example Room 101). Then associate its devices:

  1. the controlling HyperGate (mandatory);
  2. the Smart Relay;
  3. the HyperRadar presence sensor (Ultra);
  4. the HyperSensor DS contacts, if any;
  5. the trigger locks — the Luckey locks whose opening switches the space on or off.

All the devices must use the same HyperGate: a device associated with another gateway cannot be part of the unit.

Note. Once a Smart Relay is part of a Power Control Unit, it is managed as a power device and is no longer shown as a lock in the Luckey Web Application. In Luckey Web the hardware of a unit is read-only: to change it, use Luckey Tools.

Step 7 — Set the rules in the Luckey Web Application

Open Energy Management → Power Control Units, select the unit and complete its tabs:

  • Consumption settings — enter the nominal load of the space in kW, when everything is on. It is used to estimate the energy consumed and saved.
  • Automation rules — choose when the unit is switched on (HyperTag scan, opening of a trigger lock, presence detected with Ultra) and when it is switched off (HyperTag scan, opening of the exit lock, no presence after the grace period with Ultra, or a set number of minutes after power-on).
  • Who can actuate — every valid user, or only users with specific tags or that can open specific locks. Optionally enable the geolocation check, so that commands are accepted only when the user is at the building.
  • HyperSensor interaction — switch the unit off when an associated door or window is open, and back on when it is closed.

Click Save: the rules are sent to the HyperGate that controls the unit.

Step 8 — Test the space

Test every space, one by one:

  1. Switch the space on and off from the Luckey app or from the web dashboard: the load follows.
  2. Open a trigger lock: the space follows the rule you configured (for example, it switches on).
  3. Scan the HyperTag with an authorized user: the space switches on. Scan it again: it switches off.
  4. Ultra: stay still in the room — the space stays on. Leave it: the space switches off after the grace period. Come back during the grace period: the power stays on.
  5. Open a monitored window or door: the unit goes to Inhibited and the space switches off. Close it: the power comes back.
  6. Disconnect the internet connection: local switching keeps working.
  7. Check the Event history of the unit in Luckey Web: every change of state is listed with the rule or the user that caused it.

Good to know. The rules run on the HyperGate on site, not in the cloud: if the internet connection is lost, the spaces keep switching on and off, and the dashboard is updated when the connection returns.

Troubleshooting

SymptomWhat to check
The relay does not respondThe HyperGate may be out of range of the cabinet. Is the antenna outside the metal cabinet? Is the 24 V DC power supply powered?
A device cannot be associated with the unitCheck that it is within the radio range of the unit’s HyperGate: all the devices of a unit must use the same gateway.
The space switches off while someone is inside (Ultra)The room is larger than the sensor coverage (diagonal over 6 m), the sensor is outside 2.5–4.0 m, or there is an obstacle below the sensor.
The space stays on when it is empty (Ultra)Moving objects in the field (fan, curtains, plants): set exclusion zones or enable self-learning. Also check the installation height and the detection zone.
The unit stays InhibitedA HyperSensor DS reports an open door or window, or its contact is misaligned.
Users cannot switch the spaceCheck Who can actuate and, if enabled, the geolocation check.