Elevators Management

Elevator Access Control in Luckey

Elevators are one of the trickiest access points in any building: they carry people vertically through zones that would otherwise be kept separate by doors and readers. Luckey extends the same cloud-native access control model you use on doors to elevators, so you can decide exactly who is allowed to call a lift, and which floors they’re allowed to reach once inside.

This article explains how elevator access control works in Luckey, what hardware is involved, and how the system is sized for a given installation. Schematics are shown below.

The two access approaches

Every elevator in Luckey is configured with one of the following approaches:

  • Calling — readers are placed at the elevator’s landing (lobby) call point. Access control determines who can call the elevator to their floor, but once inside the cabin, the rider can press any button.
  • Floor selection — readers control the car operating panel (COP) inside the cabin. Access control determines which floor buttons a rider is allowed to press, regardless of who called the elevator.
  • Both — the two approaches are combined on the same elevator, and can optionally share a single control unit (shareUnit) to reduce hardware.

Choosing between them is mostly a question of how tightly you need to restrict floor-by-floor access:

CallingFloor selection
CostLowerSlightly higher
Control granularityRestricts access to the lift itself, not individual floors once insideFull control over which floors each rider can reach
Best fitBuildings with a public lobby and a block of private floors above itMulti-tenant buildings where different users must be limited to different, specific floors

Access medium

Riders can authenticate with any combination of:

  • Smartphone (Bluetooth Low Energy, via the Luckey app)
  • RFID card
  • PIN

The reader model needed depends on the medium mix you select:

  • Any combination of RFID and/or Smartphone → the base 1NCA reader (still commonly referred to by its earlier product name, HyperLock Stylos).
  • If PIN is required → a Keyboard reader, which also supports cards and BLE.

Control units: the key architectural rule

This is the most important thing to understand when designing an elevator installation in Luckey:

Floor selection always requires a wired HyperGate Atlas. A wireless HyperGate can control landing call buttons, but it cannot switch the relays behind the in-cabin floor buttons. Any elevator using floor selection therefore uses wired Mullion‑Lockbus readers connected to an Atlas — there is no wireless option for this approach.

Calling, on the other hand, is more flexible:

  • Smartphone-only calling readers can work completely standalone, with no control unit at all.
  • RFID or PIN calling readers need a control unit, and here you can choose any wireless HyperGate (DIN, Lite WiFi, or Lite PoE), based on your installation preferences.
  • If calling is configured to share a unit with floor selection on the same elevator, the calling readers become wired as well and join the same Atlas — you don’t run two separate control units in that case.

Sizing the HyperGate Atlas

A HyperGate Atlas provides 3 lockbus channels, each supporting up to 8 actuators — 24 actuators of capacity per unit. Luckey always starts from the base configuration (1 Powered Channel) and adds capacity as needed with:

  • 5E3502 — channel PSU, one per active channel
  • 5E000012 — lockbus expansion board, one per channel beyond the first
  • 5E3005 — Atlas PSU, one per unit

If an elevator needs to control more than 24 floors in total (calling + floor selection combined, when sharing a unit), Luckey automatically adds additional Atlas units to cover the remaining floors. 24 controlled floors per Atlas is a hard cap and cannot be exceeded within a single unit.

Bill of materials

For each elevator, the bill of materials includes:

  • 1 reader + 1 actuator per controlled floor (wired readers come bundled with their own actuator)
  • The control-unit hardware described above, sized to the configuration

Elevators follow their own power-supply logic rather than the generic rules used for doors: the standalone 30 W PSU (5E3506) used on doors doesn’t apply here, since the lockbus itself powers the reader. Elevators are also included in the overall power-budget calculation, contributing:

  • 6 W per 1NCA reader
  • 10 W per Atlas channel

Validation

When you configure an elevator in Luckey, the system automatically checks that:

  • The floor range is valid
  • At least one access medium is selected
  • Coverage counts (readers/actuators) don’t exceed the number of served floors
  • The 24-actuator Atlas cap is respected, including combined calling + floor selection totals when a unit is shared
  • A valid wireless HyperGate model is specified wherever one is required

If any of these checks fail, Luckey will flag the configuration so it can be corrected before the project is finalized.

Digital elevator integrations

For modern elevators that already run their own local or cloud-based control systems, Luckey can integrate directly via its RESTful API rather than adding physical readers to every floor. This is typically the preferred route for newer elevator installations that already expose an authorization interface, and it’s evaluated case by case during project design.

Summary

ApproachControl unitNotes
Calling, Smartphone-onlyNone requiredCable-free, standalone readers
Calling, RFID/PINWireless HyperGate (DIN, Lite WiFi, or Lite PoE)Your choice of gateway model
Floor selectionHyperGate Atlas (wired)Mandatory — no wireless option
Calling + Floor selection, shared unitHyperGate Atlas (wired)Calling readers become wired to join the Atlas

If you’re planning an elevator installation and aren’t sure which approach fits your building, our sales and technical teams can help size the right configuration based on the number of floors, tenants, and desired security level.